C-TEC's two-wire CFP AlarmSense® fire panel is designed to work with Apollo's AlarmSense® range of detectors, call points, sounders and beacons.

Most conventional fire systems are designed to work with two pairs of wires per zone: one pair for detection devices such as smoke detectors, heat detectors and manual call points; the other for alarm devices such as bells, sounders or strobes. By using different voltage bands for quiescent and alarm states, AlarmSense® components can be connected to the same pair of supply wires.

When powered and controlled by the CFP two-wire fire panel, this reliable technology takes all the complexity out of fire alarm system design, leading to quicker, less expensive and more flexible installation. Indeed, research shows an AlarmSense® two-wire system can achieve a 20-25% reduction of labour over a standard four wire conventional system.

AlarmSense®devices are acceptable for BS 5839-1 and BS 5839-6 systems making them particularly useful for fire protection in Houses of Multiple Occupation (HMOs).
C-Tec CFP AlarmSense 2 Zone Panel features:

    Intuitive user-friendly interface with colour-coded buttons and combined keypad/keyswitch entry to access level 2
    2 AlarmSense zone circuits.
    Four conventional sounder circuits
    Integral 1.5A EN54-4/A2 compliant switch mode PSU
    Wide range of engineering functions including zone test, coincidence, zone delay and non- latching zones
    Two on-board relays (Fire and Fault)
    Two open-collector outputs (Remote and Reset)
    ‘Class change’ and alert inputs
    Installer-friendly design accommodates easy first fix and straightforward maintenance
    Attractive flush or surface mountable plastic lid and enclosure - no bezel required
    Low quiescent current
    Multiple indicators
    End of line units included (one per zone)
    Ancillary system expansion connections provided for up to eight two-wire repeaters (one CFP761 network driver card required per system) and optional CFP relay boards
    Space for two x 12V 3.3Ah VRLA batteries
    Third-party LPCB tested

Technical Details
Power Supply Specification
Mains Supply Voltage:     230V ±10% 50/60Hz
Mains Rated Current:     350mA Maximum
Internal Power Supply:     19V - 28.5V (27V nominal), Ripple 7V maximum (battery fault)
Maximum Battery Size & Type:     2 x 12V 3.2Ah VRLA type, connected in series. Minimum battery size 1.2Ah
Zone Circuit Specification
Number of Circuits:     2
Max Cable Length Per Circuit:     500m
Maximum Number of Sounders Per Zone:     The panel’s powersupply is designed to give a max. output current of 1.5A. In addition to powering the sounders,this currentis also used for handling short circuit faults and supplying the panel’s battery charging circuit and any outputrelays which may be fitted. As a safe margin and to allow forthese otherloads,the totalsounderloading forthe panelshould not exceed a maximum of 1.25A. Each zone circuit and each sounder circuit willsupport a max.sounder alarm current of 200mA. Currentsin excess ofthis will cause the circuit’sfuse to trip. The soundersshould be distributed throughoutthe site according to the sound levelsrequired, butthe load should be distributed as equally as possible across each circuit.
Conventional Sounder Circuit Specification (for use with non-AlarmSense Sounders)
Number of Circuits:     4
Alarm Voltage:     27V maximum, 20V minimum (final battery voltage)
Maximum Total Sounder Output Current to all Outputs:     4 x 200mA = 800mA
Maximum Number of Bells @ 25mA     32
Maximum Number of Electronic Sounders @ 20mA     40 (Sounders must be Polarised)
Dimensions
Physical Size:     Size = W:380 x H:235 x D:96mm approx.
Weight:     1.75kg (Without Batteries)

Write a review

Note: HTML is not translated!
    Bad           Good

When you order from opencartworks.com, you will receive a confirmation email. Once your order is shipped, you will be emailed the tracking information for your order's shipment. You can choose your preferred shipping method on the Order Information page during the checkout process.

The total time it takes to receive your order is shown below:

The total delivery time is calculated from the time your order is placed until the time it is delivered to you. Total delivery time is broken down into processing time and shipping time.

Processing time: The time it takes to prepare your item(s) to ship from our warehouse. This includes preparing your items, performing quality checks, and packing for shipment.

Shipping time: The time for your item(s) to tarvel from our warehouse to your destination.

Shipping from your local warehouse is significantly faster. Some charges may apply.

In addition, the transit time depends on where you're located and where your package comes from. If you want to know more information, please contact the customer service. We will settle your problem as soon as possible. Enjoy shopping!